Is it possible for connecting a non-incendive Ex nA digital indicator to an intrinsically safe Ex i sensor in hazardous areas? Frequently, signals from pressure sensors that not have a built-in digital indicator for the measured value are linked to external digital indicators. These digital indicators enable an on-site display of the measured value and, thus, a convenient and immediate reading of, for example, the particular level in storage vessels.
Pressure sensors for hazardous areas are frequently made with the ignition protection type ?intrinsically Atrocious ?, since this enables interventions within an active electrical circuit and less energy is necessary. However, this also implies that there is insufficient energy available for a powerful measured value display. As a result, digital indicators are often designed with ignition protection types that enable more current and voltage to be allowed. Frequently, digital indicators are designed as ?non-incendive? (Ex nA). This ignition protection type enables power-hungry instruments to be operated in Ex areas too. However, Ex nA is limited for used in zone 2 ? so in areas in which an explosive atmosphere only rarely occurs.
The right connection of digital indicator and barrier
Non-permissible connection of an Ex i pressure sensor with isolated barrier and Ex nA digital indicator.
Every Ex i sensor requires an intrinsically safe barrier because of its voltage supply, so the interconnection is considered as intrinsically safe and the benefits, such as for example maintenance work without the need for a fire certificate, can be utilized. Digital indicators are generally integrated as passive element, with or lacking any external power, directly in the 4 ? 20 mA current signal of a sensor. Since an Ex nA digital indicator does not have any Ex i performance data in its approval, it cannot therefore be used in a ?Proof of intrinsic safety?. Therefore, an Ex nA indicator can’t be connected within an Ex i circuit.
Correct connection of an Ex i pressure sensor with isolated barrier and Ex nA digital indicator.
There is, however, the possibility to connect a digital indicator with an Ex i pressure sensor in zone 2. Volatile is that the intrinsically safe isolated barrier also possesses an Ex nA approval and should be installed in zone 2.
Read also our articles
Ex barrier and intrinsically safe pressure sensors ? Perspective for an ATEX-approved pressure sensor
Note
In the event you need any help with selecting a suitable solution for your pressure measurement requirement, your contact person will gladly be of assistance.